Multifunction Electric Meters C284Z-2S4_DC284Z-9S4
1.     Summarize

Z series multifunction meters are intelligent power distribution meters with high precision, high reliability, high cost efficiency, they are designed for the applications such as electric power monitoring, intelligent control, measuring assessment with voltage system, industrial and mining enterprises, public facilities, intelligent buildings and so on. The series meters adopt high precision special metering chip and high reliability MCU design, can 
measure all electric parameters of the three-phase electric power grid, such as three-phase voltage (phase/wire), three-phase current, active power, reactive power, power factor, electric power grid frequency, UIPQ demand and bidirectional electric power metering, with standard electric energy pulse output and RS485 communication interface, can choose various function expansion module. The series products with high cost-effective feature can replace general electric power transmitters, measurement indication meters, electric energy metering meters and relative assistant units. As one kind of advanced intelligent, digital electric grid frontend collection components, Z series multifunction electric power monitoring meters are widely used in a variety of control systems, SCADA systems and energy management system, substation automation, distribution network automation, community electric power monitoring, industrial automation, intelligent building, intelligent distribution cabinet, switchgear cabinet, with the features of easy installation, simple wiring, easy maintenance, small quantities project, they can be programmable to set input parameters in site work, they can complete different PLC, control computer communication software group network industrially.

The products meet the standard of GB/T22264.1-2008, GB/T 13978-2008.

2.      Typical Product Pictures

3.     Models and Meaning of Products

4.     Products Models

Model

Product function

DC284Z-2S4

DC284Z-9S4

Real-time measurement

Three-phase voltage

Three-phase current

Active power

Reactive power

Apparent power

Power factor

Frequency

Electric energy metering

Active electric energy

Reactive electric energy

Bi-directional metering

Harmonic wave

2-31 times of odd harmonic component

-

-

Real-time clock

Year, Month, Date, Hour, Minute, Second

-

-

Electric energy pulse

Passive stem node

2

2

Analog output

AO (DC4-20mA)

4

4

On-off output

(Relay output)

DO/RO (AC400V/0.1A,

or AC250V/5A)

4

4

On-off input

DI (Passive stem node)

4

4

Communication interfa, ce

RS485, Modbus-RTU

Display mode

LED

LED

Panel size (mm)

120x120

96x96

Hole size (mm)

111x111

91x91

Installation mode

Panel Mounting

Panel Mounting

Remark:

1)     ” means the model has the function.

2)     “ - “ means the model doesn’t have such function.

3)     The number means channel, for example: 2 means the model has the function with 2 channels.

5.     Technical Specifications

Description

Parameters

Precision grade

Electric capacity metering: active electric energy: 0.5 class, reactive electric energy grade:1.0, transmission output grade 0.5

Display mode

LED display

Input signal

Measurement network

Three-phase four-wire V34/Three-phase three-wire V33

Voltage

Rated voltage

AC100V, AC400V

Excess load

Continuance: 1.2 times; Instantaneous: 2 times (10s)

Power consumption

0.6VA (each phase)

Impedance

200kΩ

Current

Rated current

AC5A / AC1A

Excess load

Continuance: 1.2 times; Instantaneous: 10 times (5s)

Power consumption

0.4VA (each phase)

Impedance

20mΩ

Frequency

45-65Hz (0.01Hz)

Electric energy

Bi-directional Active/Reactive electric energy metering

Power supply

Working scope

AC/DC 85-264V

Power consumption

5VA

Function modules

Electric energy pulse

Passive optical coupler collector output

Communication interface

1-way RS485 communication interface, Modbus-RTU Protocol

On-off input

Passive stem node

On-off output

Excess alarm or remote relay output capacity AC5A/250V, AC/DC/0.1A /400V

Transmission output

0-20mA/4-20mA/0-5V/1-5V transmission output, programmable to setting transmission items and relative output data.

Security

Insulation resistance

100MΩ

Resist pressure

Input voltage1kV,  Input and output2kV, Power supply and output2kV

Work environment

Temperature

-10℃~55

Relative humidity

93RH

Altitude

Non-corrosive gas forum, Altitude 2500m

storage environment

Temperature

-20℃~75

Relative humidity

93RH

6.     Outline Dimension

DC284Z-2S4

DC284Z-9S4

7.     Typical Functions Terminal Numbering

8.     Typical Signal Input Wiring Diagram

Note: the above diagram is only for reference, the actual parameters in the factory shall prevail.

Wiring Instruction:

l   Input voltage cannot exceed rated input voltage (100V or 400V), otherwise should consider using PT, in order to make maintenance easily, advice to use connector bar.

l   Standard rated input current is 5A or 1A, if in the situation of more than 5A, should use exterior CT. If using CT with other meters, wiring method should be series connection, before removing the wire of input current, make sure that cut off CT one circuit or Short sub-secondary circuit in advance, in order to make maintenance easily, advice to use connector bar.

l   Make sure input voltage is correspond with input current, phase no. consistent, directions are consistent, otherwise the value and the symbol of power and electric energy will be wrong.

l   The meter can work in three-phase four-wire or three-phase three-wire mode, the users should select the appropriate wiring way based on the site situation. Usually under the situation without center line, use three-phase three-wire mode, while three-phase four-wire mode under the situation of center line. Please pay attention that onsite wiring mode must be consistent with the wiring default setting of the meter, otherwise the data of measured by meters will be incorrect.

9.     Ordering Example

l   Model: DC284Z-2S4

l   Signal Input: AC10kV/0.1kv, AC200A/5A

l   Wire Connection Mode: three-phase three-wire (2CT, 2PT)

l   Transmission Output: 4-ways

Transmission 1: DC4-20mA corresponds to Uab

Transmission 2: DC4-20mA corresponds to Ia

Transmission 3: DC4-20mA corresponds to Psum

Transmission 4: DC4-20mA corresponds to Qsum

l   Communication: RS485

l   Other: other factory pre-sets (if no indication when ordering, ex-factory products will be delivered in accordance with the default setting).

BACK